JWD1-6T Screw Type Switching TB for Circuit Break Capacity

JWD1-6T Screw Type Switching TB for Circuit Break Capacity

1. Wiring gauge: 0.2-6mm².

2. Left and right conductive parts disconnected; the center knob connect at clockwise and disconnects counterclockwise.

3. Utilizes a screwdriver, featuring high clamping force and maintenance-free operation. This type of terminal block supports multi-wire connections at a single connection point, allowing for wire connection without pretreatment.

4. Enables multi-digit shorting or bridging.

5. Markers meet the marking needs of users in different scenarios.

  • Product Description
  • Parameters
  • Certification
Terminal thickness: 8mm, Mini terminal block
Rigid wireFlexible wireIUi
(mm2)(A)(V)
0.2-100.2-657500
IEC 60947-7-1

TypePart NumberPackage quantity


DescriptionSchematic diagramType
Test terminal:JWD1-6T
With general-purpose locating base, suitable for standard mounting rails
and

Switching terminal:
With general-purpose locating base, suitable for standard mounting rails
and

(1) End plate:
One additional piece must be attached to the end of each terminal strip set. If it is mounted in the center of the terminal strip, the creepage distance may increase.
(2) Central liaison part:JWD9-ZL 8/2
It is used to connect terminals with the same specification and form a liaison terminal group; each part has 10 digits (supplied with screws) that can be further divided at will.JWD9-ZL 8/3

JWD9-ZL8/4

JWD9-ZL8/10
(3) Edge liaison part2 digits:JWD9-BL 8/2
Its role is the same as that of the central liaison part (2); with insulation on the back side; 10 digits that can be further divided at willJWD9-BL 8/3

JWD9-BL8/4

JWD9-BL8/10

3 digits:

10 digits:
(4) Divider:
It is used to separate two adjacent liaison terminal groups and can be inserted after assembly, without any effect on the overall space.
(5) Group partition:
Used for separation of each terminal group; with dual effects (visible grouping and electrical isolation)
(6) Central liaison partJWD9-LJ 8/2
It is used to connect terminals with the same specification and form a liaison terminal group; each part has 10 digits (supplied with screws) that can be further divided at will.
(7) Switch liaison part
It can be used on both sides of the breaking sliding block for two terminals; the strap of the liaison part is pushed inwards to make it break; two screws are supplied.
(8) Switch liaison part
It can be used on both sides of the breaking sliding block for two terminals; the strap of the liaison part is pushed outwards to make it break; two screws are supplied.
(9) Switch liaison part
It is used for two terminals; please note that it can only be used on the right of terminals; two screws are supplied.
(10) Switch liaison part
It is used for the short circuit of a three-phase interconnected current transformer and can only be used on the right of the terminal; 1) four screws are supplied.
(11) Test plug:
ZP9.5/8-10
(12) Conversion test plug:
(13) Tag:


Terminal dimensions

Thickness / width / end plate thickness[mm]8/51.2/-
Height (TH 35:7.5 / TH 35:15 / G 32:15)[mm]46/53.5/-
Technical data based on IEC/DIN VDE standards

Maximum rated working current / cross-sectional area[A]/ [mm]Jun-57
Maximum cross-sectional area of conductors (rigid / flexible) that can be connected if any edge liaison part is use side plug in bridges[mm2]6/6
Rated impulse withstand voltage / degree of pollution[kV]/-6/3
Over-voltage category / insulation material group-/-lll/l
Connection capacity

Flexible conductor with tubular bare terminal / tubular pre-insulated terminal[mm2]0.5-6/0.5-4
Connection of multiple conductors (connecting two conductors with the same cross-sectional area)

Rigid conductor / flexible conductor[mm2]0.5-2.5/0.5-6
Flexible conductor with tubular bare terminal[mm2]0.5-4
Flexible conductor with DEV-tubular pre-insulated terminal[mm2]0.5^
Stripping length[mm]12
Screw for terminal position: screw / torque[Nm]M4/1.5-1.8
Screw for breaking sliding block: screw / torque[Nm]-
Insulation material type
PA
Material flammability according to UL94
V0
Rated working voltage / rated working current / wire gaugeUL:[V]/[A]/AWG300/50/26-8


ce
eac
rohs
ul with r certificate
Welcome to consult us for more information!