JWD2-2.5a/2-L/N Spring Cage Double Layers(Upper L/Lower N) Terminal Block

JWD2-2.5a/2-L/N Spring Cage Double Layers(Upper L/Lower N) Terminal Block

1. Wiring range: 0.2-2.5mm².

2. Four wiring positions with independent upper and lower layers: upper layer for live wire, lower layer for neutral wire.

3. Simple wiring for extremely flexible conductors.

4. Uses spring-loaded contact elements for reliable vibration resistance.

5. No limitation on wiring capacity when using conductors with cold-pressed heads.

6. Flat marking strip for quick marking.

  • Product Description
  • Parameters
  • Certification

Double-Layer Phase Conductor & Ground Type

Double-Layer Null Line & Ground Type

Double-Layer Phase Conductor & Null Line Type

(IEC)(mm2)Rigid solidFlexible multi-conductorI(A)Ui(V)
DIN VDE 06110.2-40.2-2.532500


DescriptionColorSchematic diagramType


Spring-cage terminal mounted onGrey
JWD2-2.5a/2-L/N


(1) End plateGreyG-D2-2.5a/2
(2) Plug in bridge used for horizontal connection in the terminal center2 ports
FBS 2-5Imax: 20A



3 ports
FBS 3-520A



4 ports
FBS 4-520A



5 ports
FBS 5-520A



10 ports
FBS 10-520A



20 ports
FBS 20-520A


(3) Partition plate used to isulate the terminal block assembly
GF-D2-a/2


(4) Double-tagging bracket inserted in the double-layer spring-cage terminal JWD2…/2, identified with ZP5 and ZBFM5
ZP-a/ZJ2


(5) Warning panel mounted at the operation port of the D2 "Miniature Spring" spring-cage terminal
WST2.5


(6) Screwdriver
SZF 1-0.6X3.5


(7) Markers strip, with 100 units for lateral identificationWhiteZBFM5


(8) Test plugGrey




Terminal dimensions

Thickness / length / end plate thickness[mm]5.2/67.5/2.2
Height (TH 35:7.5 / TH 35:15)[mm]47.5/55
Technical data in accordance with IEC/DIN VDE standards

Maximum rated working current / cross-sectional area[A] / [mm2]26/4
Rated impulse withstand voltage / degree of pollution[KV] / -6/3
Over-voltage category / insulation material group- / -III/I
Connection

Flexible wire with ferrule[mm2]0.25-2.5
Flexible wire with cable lug[mm2]0.25-2.5



Stripping length[mm]10
Plug gauge (IEC60947-1)
A3
Insulation material
PA
Grading as per UL 94
V0
Certification data (UL and CSA/CUL)

Rated working voltage / rated working current / wire gaugeUL: [V]/[A]/AWG300/20/26-12
CSA/CUL: [V]/[A]/AWG-