Email Us
JWD1-50JD Screw Type High-Current Din-Rail TB

JWD1-50JD Screw Type High-Current Din-Rail TB

1. Wiring range: 25-50mm².

2. Utilizes a screw self-locking principle, featuring high clamping force and maintenance-free operation. This type of terminal block supports multi-wire connections at a single connection point, allowing for wire connection without pretreatment.

3. The high-current terminal block's structural design ensures reliable connection of large-section wires.

4. Enables multi-digit shorting or bridging.

5. Marking strips meet the marking needs of users in different scenarios.

6. Can be used in areas with explosion hazards (according to IEC/EN 60079).

7. Unique spring-loaded rail structure allows for convenient and quick installation on guide rails.

8. Equipped with a grounding pin for rapid grounding.

  • Product Description
  • Parameters
  • Certification
Terminal thickness: 20

Rigid conductorFlexible conductor

(mm2)
IEC 60947-7-216-5025-50


Description
Type
Ground Terminal:
The yellow-green insulating housings can be mounted on the mounting rails

JWD1-50 JD
Edge liaison part:
Its role is the same as that of the central liaison part (2); with insulation on the back side; 10 digits that can be further divided at will
2 digits:
3 digits:
10 digits:
Edge liaison part:
Its role is the same as that of the central liaison part; with insulation on the back side, inserted in the conductor holder, and clamped on the insulation housing of the terminal
2 digits
3 digits
Prismatic conductor holder:
A prismatic metal block used to compensate the pressed flat conductor

50 EP
Terminal fastener: (thickness: 10)
It is used to finally fix a large-current terminal; after it is pushed, it can be mounted on Type TH35/15 mounting rail, and it should be fixed with two screws.

ZG2
Tag:
It can be quickly inserted in the upper grooves on both sides of the terminal as a whole for any identification. It has a total of 10 digits (to be divided at will); it is white.

ZP10
Terminal dimensions
Thickness / width / end plate thickness[mm]20/70.5
Height (TH 35:7.5 / TH 35:15 / G 32:15)[mm]83.5/81.5
Technical data based on IEC/DIN VDE standards

Maximum rated working current / cross-sectional area[A] / [mm2]150/50
Rated impulse withstand voltage / degree of pollution[kV]/-8/31)
Over-voltage category / insulation material group-/-III/I
Connection capacity

Flexible conductor with tubular bare terminal / tubular pre-insulated terminal[mm2]25-50 / 25-50
Connection of multiple conductors (two conductors with the same cross-sectional area)

Rigid conductor / flexible conductor[mm2]10-16/10-16
Flexible conductor with tubular bare terminal[mm2]45581
Flexible conductor with DEV-tubular pre-insulated terminal[mm2]-
Stripping length[mm]24
Screw for terminal position: screw type / torque-/[Nm]M 6*/ 6-8
Central fastening screw: screw type / torque-/[Nm]M 6*/ 6-8
Insulation material type
PA
Material flammability according to UL94
V0
Rated working voltage / rated working current / wire gaugeUL:[V]/[A]/AWG-/-/6-1/0
Note: When an edge liaison part is used, a cable below 1.5 mm2 should be used for a 2.5 mm2 terminal; corresponding cables should be used for terminals with other cross-sectional areas (mm2).